LEED Certification for Homes – MR PREREQUISITE: DURABILITY MANAGEMENT
Requirements
HOMES, MIDRISE
Meet the requirements of the ENERGY STAR for Homes, version 3, water management system builder checklist (with the exceptions for existing homes listed in EA Prerequisite ENERGY STAR for Homes Performance).
Midrise projects are exempt from this requirement.
Install all the applicable indoor moisture control measures listed in Table 1.
Table 1. Required interior moisture control measures for homes
Location or equipment | Required measure |
Area directly above bathtub, spa, or shower (extending to ceiling), exposed wall or area behind fiberglass enclosure if wallboard is installed | Use nonpaper-faced backer board or paper-faced product or coating over wallboard that meets standard ASTM D 3273 standard |
Kitchen, bathroom, laundry room, spa area | Use water-resistant flooring; do not install carpet |
Entryway within 3 feet (900 mm) of exterior door accessible from ground | Use water-resistant flooring; do not install carpet (carpet tiles are permitted) |
Tank water heater in or over living space | Install drain and drain pan, drain pan and automatic water shut-off or flow restrictor, or floor drain with floor sloped to drain |
Clothes washer (or condensing clothes dryer) in or over living space | Install drain and drain pan, drain pan and automatic water shut-off or flow restrictor, or floor drain with floor sloped to drain |
Conventional clothes dryer | Exhaust directly to outdoors |