LEED Certification for Homes – EA CREDIT: AIR INFILTRATION
Requirements
HOMES
Case 1. Single Family
Meet the air leakage requirements shown in Table 1 or Table 2. The rate of air leakage to outside must be tested and verified by a qualified energy rater.
Case 2. Multifamily
Meet the air leakage requirements shown in Table 1 or Table 2. The rate of air leakage to outside must be tested and verified by a qualified energy rater.
Meet the requirements for leakage to outside the conditioned envelope for each dwelling unit, unless the whole building can be entirely and sufficiently depressurized by a blower door(s).
ACH = Air changes per hour cfm = cubic feet per minute
ELR = envelope leakage ratio
IECC = International Energy Conservation Code sf = square feet
cmm = cubic meters per minute