LEED Certification for Homes – EA PREREQUISITE: HOME SIZE

Published by firstgreen on

Requirements

HOMES

Earn 1 point for every 4% decrease in conditioned floor area compared with the ENERGY STAR for Homes, version 3, reference home (Table 1).

Buildings that are larger than the reference home lose 1 point for every 4% increase in conditioned floor area.

Projects cannot exceed the maximum number of points in the EA section.

Table 1. Conditioned floor area of reference home, by number of bedrooms
Bedrooms12345678 or more
Floor area (square feet)1,0001,6002,2002,8003,4004,0004,600+ 600 ft2 per additional bedroom
Floor area (square meters)93148204260315371427+ 55 square meters per additional bedroom

For multifamily buildings, home size includes only in-unit space.