Earthing is one of the most critical safety systems in a solar photovoltaic (PV) installation. While PV modules and inverters generate clean energy, improper or inadequate earthing can expose equipment and personnel to serious electrical hazards. The image illustrates a comprehensive earthing scheme covering the PV array, inverter, DCDB, ACDB, and the main earth network, aligned with standard engineering practices and Indian Standards such as IS 3043.


1. Purpose of Earthing in Solar PV Systems

The primary objectives of earthing are:

  • Protection of personnel from electric shock
  • Safe dissipation of fault and leakage currents
  • Equipment protection against insulation failure and surges
  • Stable reference potential for system operation

In solar PV plants, earthing is not optional; it is a mandatory requirement for electrical safety and statutory approval.


2. PV Array Earthing

The left side of the diagram focuses on PV array earthing, which includes:

  • PV Modules and Mounting Structure
    All metallic parts of module frames and mounting structures must be electrically bonded.
  • Array Frame Earthing
    Each row or table is connected to the PV structure earth bar using appropriately sized conductors.
  • Standards Compliance
    Earthing connections follow IS 3043, which governs earthing practices in India.

Key requirements include:

  • Tight mechanical bonding of all metallic parts
  • Use of rust-free connections
  • Regular inspection and testing

Failure to properly earth the array increases the risk of shock and lightning-related damage.


3. Inverter, DCDB, and ACDB Earthing

The right section highlights equipment earthing:

  • DCDB Body Earthing
    The DC Distribution Box enclosure must be bonded to the earth network.
  • Inverter Earthing (PE)
    The inverter protective earth terminal is connected using green/yellow PE cables, typically sized between 6–16 sq.mm, depending on system rating.
  • ACDB Earthing
    The AC Distribution Board enclosure and internal earth busbar are connected to the same earthing network.

All equipment earthing points must be clearly labeled and accessible for inspection.


4. Main Earthing Network and MEBB

A central feature of the diagram is the Main Earthing Network, incorporating a Main Earth Busbar (MEBB):

  • Acts as a common bonding point for all earth connections
  • Prevents potential differences between system components
  • Enables controlled fault current flow

Avoiding looping is critical; instead, a star or radial topology from equipment to the MEBB is recommended.


5. Fault Current Flow and Safety

The illustrated fault current flow path shows how:

  • Leakage or fault current travels safely through the earth conductor
  • Energy is dissipated into the earth electrode system
  • Protective devices operate correctly

A continuous, low-resistance path is essential for rapid fault clearing.


6. Earth Electrodes and Earth Pit Design

The earth pit shown includes:

  • Earth electrodes (minimum one recommended, more for redundancy)
  • Charcoal and salt layers to improve soil conductivity
  • Compliance with IS 3043 earth pit construction guidelines

Earth resistance values must be tested periodically, with results documented as part of O&M records.


7. Cable Selection and Installation Best Practices

Best practices emphasized include:

  • Use of green/yellow insulated PE cables
  • Appropriate conductor sizing based on system capacity
  • UV-resistant and corrosion-resistant materials
  • Secure mechanical terminations

Improper cable sizing or loose terminations can render the earthing system ineffective.


8. Inspection, Testing, and Maintenance

Effective earthing requires:

  • Annual earth resistance testing
  • Visual inspection of all bonding points
  • Replacement of corroded connectors
  • Verification of continuity between components

Neglecting earthing maintenance is a common cause of safety incidents and equipment failure.


9. Compliance and Regulatory Expectations

Electrical inspectors and utilities expect:

  • Separate earthing for PV systems where required
  • Clear documentation and test reports
  • Compliance with IS 3043 and applicable IEC standards

Non-compliance can delay commissioning or result in unsafe operation.


Conclusion

A properly designed and executed earthing system is the backbone of solar PV safety. From PV arrays and inverters to DCDBs, ACDBs, and earth pits, every metallic component must be bonded into a unified earthing network. Adhering to standards, following best practices, and maintaining the system over time ensures safe operation, equipment protection, and long-term reliability of solar PV installations.


0 Comments

Leave a Reply

Avatar placeholder

Your email address will not be published. Required fields are marked *